100 kW reference configuration

Technical specification

Power, cooling, fire protection, monitoring, security, enclosure and testing for a factory-built container data centre, as delivered for the 100 kW reference unit.

  • 43.4 m²Internal floor area
  • PUE 1.3 to 1.4Measured in operation
  • −30 °CCold climate option

Specification

Reference configuration: 100 kW, ten cabinets

Every unit is engineered around the client's load, redundancy and site. These are the standard values.

Power

Redundancy2N (A and B feeds) or N+1
UPSModular, lithium-ion, expandable in 30 kW steps
AutonomyTypically 15 minutes
DistributionA/B panels, two monitored PDUs per cabinet, metering per cabinet
InterfacesGenerator and solar where specified

Cooling

SystemIn-row DX precision cooling, N+1, with reheat and humidity control
ContainmentHot aisle containment
Heat rejectionOutdoor air-cooled condensers on integrated end frames
Climate optionsDry cooler and free cooling for Nordic and Baltic sites; cold climate specification down to −30 °C
High densityRear door cooling to 60 to 70 kW per cabinet; liquid cooling engineered per project

Fire protection

SuppressionNovec 1230 clean agent
DetectionSmoke detection, separate protection for electrical panels
OptionVESDA early detection
StandardsEN 15004 and EN 54

Monitoring

DCIMAsset, capacity and power management
SensorsTemperature, humidity, water leak, three phase voltage and door
IntegrationSNMP and Modbus to your BMS or SCADA
AlarmsEmail and SMS notification

Security

AccessCard and PIN; biometric options
SurveillanceIP CCTV inside and along the perimeter
ShellNo windows, sealed cable entries, plant separated from IT space
Hardened optionBurglar resistance class RC4 to EN 1627

Enclosure

Dimensions13,550 × 3,200 × 2,900 mm
Overall with condensers19,550 mm
Internal floor area43.4 m², about 46% more than a 40 ft high cube (29.7 m²)
ProtectionIP55, 150 mm rock wool insulation
MountingSeismic isolation mounts available
SitePrepared concrete slab, 5,200 mm wide

Cabinets and cabling

Cabinets42U, 800 × 1100 mm
Density10 to 15 kW standard, up to 20 kW air cooled
Cabling24 copper and 24 fibre links per cabinet as standard

Testing and engineering

Factory testAcceptance test with load bank before shipment
On siteInstallation and commissioning in 7 to 10 days
DocumentsCabinet elevations, single-line diagrams, load calculations, bill of quantities, project specification
HandoverAs-built drawings, test records, O&M manuals, operator training
Warranty2 years, including maintenance

Standards

DesignEN 50600 principles
AvailabilityRedundancy designed to the agreed Tier level; Uptime Institute certification as an option
ThermalASHRAE thermal guidelines
FireEN 15004, EN 54
ConformityAll equipment CE marked

Sizes

Sized to the requirement, not to a catalogue

Usual working range. The same enclosure can carry more cabinets at lower density, or fewer at higher density.

25 kW2 to 3 cabinets
50 kW4 to 6 cabinets
75 kW6 to 8 cabinets
100 kW10 cabinets (reference)
150 kW8 to 10 cabinets at higher density
Cabinet elevation drawing for a container data centre, showing planned equipment positions in every cabinet
Every cabinet drawn before manufacture.

FAQ

Technical specification: questions

Not answered here? Ask us directly. We reply within a few hours.

Request a budget price

Can the unit run in cold climates?

Yes. It can be specified for outdoor temperatures down to −30 °C, and in Nordic and Baltic climates free cooling improves efficiency further.

What rack density is possible?

10 to 15 kW per cabinet as standard and up to 20 kW air cooled. Rear door cooling supports 60 to 70 kW per cabinet for AI and GPU workloads.

Do we receive drawings before manufacture?

Yes. Cabinet elevations, single-line diagrams and a project-specific technical specification are issued for approval before the unit is built.

Budget price

Request a budget price

Three figures are enough to start: IT load, site and date. We reply within a few hours, with a budget price within 48 hours.

48hBudget price and an outline configuration. Specification and drawings follow once the scope is agreed.